Standards
EMC Immunity Tests
Fast transient disturbance immunity test (Burst)
IEC 60255-22-4
IEC 61000-4-4
class 4
Power supply, mains inputs
Other in- and outputs
±4 kV, 2.5 kHz
±2 kV, 5 kHz
Surge immunity test (Surge)
IEC 60255-22-5
IEC 61000-4-5
class 4
Within one circuit
Circuit to earth
2 kV
4 kV
class 3
Communication cables to earth
2 kV
Electrical discharge immunity test (ESD)
IEC 60255-22-2
IEC 61000-4-2
class 3
Air discharge
Contact discharge
8 kV
6 kV
Radiated radio-frequency electromagnetic field immunity test
IEC 60255-22-3
IEC 61000-4-3
26 MHz – 80 MHz
80 MHz – 1 GHz
1 GHz – 3 GHz
10 V/m
35 V/m
10 V/m
Immunity to conducted disturbances induced by radio frequency fields
IEC 61000-4-6
class 3
150kHz - 80MHz
10 V
Power frequency magnetic field immunity test
IEC 61000-4-8
class 4
continues
3 sec
30 A/m
300 A/m
641
MRI4
DOK-HB-MRI4-2E
Содержание highprotec MRI4
Страница 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Страница 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Страница 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Страница 56: ...Installation and Connection Ethernet RJ45 Terminals 56 MRI4 DOK HB MRI4 2E 1 8 TxD TxD RxD n c n c RxD n c n c...
Страница 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Страница 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Страница 373: ...373 MRI4 DOK HB MRI4 2E...