Communication Protocols
Parameter
Description
Setting range
Default
Menu path
Scale Factor 26 The scale factor is used to convert the
measured value in an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP3
/Point map
/Analog Input]
Dead Band 26
If a change of measured value is greater
than the deadband value it will be reported
to the master.
0.01 - 100.00% 1%
[Device Para
/DNP3
/Point map
/Analog Input]
Analog value
27
Analog value can be used to report values
to the master (DNP)
1..n,
TrendRecList
-.-
[Device Para
/DNP3
/Point map
/Analog Input]
Scale Factor 27 The scale factor is used to convert the
measured value in an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP3
/Point map
/Analog Input]
Dead Band 27
If a change of measured value is greater
than the deadband value it will be reported
to the master.
0.01 - 100.00% 1%
[Device Para
/DNP3
/Point map
/Analog Input]
Analog value
28
Analog value can be used to report values
to the master (DNP)
1..n,
TrendRecList
-.-
[Device Para
/DNP3
/Point map
/Analog Input]
278
MRI4
DOK-HB-MRI4-2E
Содержание highprotec MRI4
Страница 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Страница 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Страница 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Страница 56: ...Installation and Connection Ethernet RJ45 Terminals 56 MRI4 DOK HB MRI4 2E 1 8 TxD TxD RxD n c n c RxD n c n c...
Страница 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Страница 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Страница 373: ...373 MRI4 DOK HB MRI4 2E...