Measuring Values
Energy Units (applies only for devices with energy measurement)
By means of the parameter »
Energy Units« the User can determine how measured values are to be displayed
within the HMI and
Smart view:
Energy Auto Scaling
kWh, kVArh or kVAh
MWh, MVArh or MVAh
GWh, GVArh or GVAh
In case of an overflow of the counter, the counter will start counting again at zero. A corresponding signal will
indicate the counter overflow.
Counter overflow at:
Energy Auto Scaling
Depends on the settings for the current and voltage transformers
kWh, kVArh or kVAh
999,999.99
MWh, MVArh or MVAh
999,999.99
GWh, GVArh or GVAh
999,999.99
Temperature Unit
(applies only for devices with temperature measurement)
By means of the parameter »
Temperatur Unit« the User can determine how measured values are to be displayed
within the HMI and
Smart view:
° Celsius
° Fahrenheit
Cutoff level
In order to suppress noise within measured values that are close to zero the user has the option to set cutoff levels.
By means of the cutoff levels, measuring quantities that are close to zero will be displayed as zero. These
parameters have no impact on recorded values.
134
MRI4
DOK-HB-MRI4-2E
Содержание highprotec MRI4
Страница 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Страница 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Страница 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Страница 56: ...Installation and Connection Ethernet RJ45 Terminals 56 MRI4 DOK HB MRI4 2E 1 8 TxD TxD RxD n c n c RxD n c n c...
Страница 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Страница 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Страница 373: ...373 MRI4 DOK HB MRI4 2E...