Service and Commissioning Support
Device Planning Parameters of the Failure Simulator
Parameter
Description
Options
Default
Menu path
Mode
Mode
do not use,
use
use
[Device planning]
States of the Inputs of the Failure Simulator
Name
Description
Assignment via
Ex Start
Simulation-I
State of the module input:External Start of Fault
Simulation (Using the test parameters)
[Service
/Test (Prot inhibit)
/Sgen
/Process]
ExBlo1-I
Module input state: External blocking1
[Service
/Test (Prot inhibit)
/Sgen
/Process]
ExBlo2-I
Module input state: External blocking2
[Service
/Test (Prot inhibit)
/Sgen
/Process]
Ex ForcePost-I
State of the module input:Force Post state. Abort
simulation.
[Service
/Test (Prot inhibit)
/Sgen
/Process]
Signals of the Failure Simulator (States of the Outputs)
Signal
Description
Manual Start
Fault Simulation has been started manually.
Manual Stop
Fault Simulation has been stopped manually.
Running
Signal; Measuring value simulation is running
Started
Fault Simulation has been started
Stopped
Fault Simulation has been stopped
State
Signal: Wave generation states: 0=Off, 1=PreFault, 2=Fault, 3=PostFault,
4=InitReset
626
MRI4
DOK-HB-MRI4-2E
Содержание highprotec MRI4
Страница 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Страница 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Страница 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Страница 56: ...Installation and Connection Ethernet RJ45 Terminals 56 MRI4 DOK HB MRI4 2E 1 8 TxD TxD RxD n c n c RxD n c n c...
Страница 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Страница 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Страница 373: ...373 MRI4 DOK HB MRI4 2E...