![Woodward highprotec MRI4 Скачать руководство пользователя страница 532](http://html1.mh-extra.com/html/woodward/highprotec-mri4/highprotec-mri4_user-manual_995900532.webp)
Protective Elements
Parameter
Description
Setting range
Default
Menu path
t-DP4
Dead time between trip and reclosure
attempt for phase faults.
Only available if: Shots = 4-6
0.1 - 9999.00s
1s
[Protection
Para
/<1..4>
/AR
/Shot Manager
/Shot Ctrl4]
t-DP5
Dead time between trip and reclosure
attempt for phase faults.
Only available if: Shots = 5-6
0.01 - 9999.00s 1s
[Protection
Para
/<1..4>
/AR
/Shot Manager
/Shot Ctrl5]
t-DP6
Dead time between trip and reclosure
attempt for phase faults.
Only available if: Shots = 6
0.01 - 9999.00s 1s
[Protection
Para
/<1..4>
/AR
/Shot Manager
/Shot Ctrl6]
t-DE1
Dead time between trip and reclosure
attempt for earth faults
Only available if: Shots = 1-6
0.01 - 9999.00s 1s
[Protection
Para
/<1..4>
/AR
/Shot Manager
/Shot Ctrl1]
t-DE2
Dead time between trip and reclosure
attempt for earth faults
Only available if: Shots = 2-6
0.01 - 9999.00s 1s
[Protection
Para
/<1..4>
/AR
/Shot Manager
/Shot Ctrl2]
t-DE3
Dead time between trip and reclosure
attempt for earth faults
Only available if: Shots = 3-6
0.01 - 9999.00s 1s
[Protection
Para
/<1..4>
/AR
/Shot Manager
/Shot Ctrl3]
532
MRI4
DOK-HB-MRI4-2E
Содержание highprotec MRI4
Страница 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Страница 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Страница 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Страница 56: ...Installation and Connection Ethernet RJ45 Terminals 56 MRI4 DOK HB MRI4 2E 1 8 TxD TxD RxD n c n c RxD n c n c...
Страница 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Страница 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Страница 373: ...373 MRI4 DOK HB MRI4 2E...