8 Process data
| Process input data
50
2547720000/03/09.2019
Manual Communication module UR20-4COM-IO-LINK
8.2 Process input data
Process data inputs UR20-4COM-IO-LINK
Byte
Bit
Description
IB0
IX0.0
DI 1
IX0.1
DI 2
IX0.2
DI 3
IX0.3
DI 4
IX0.4
C/Q 1
IX0.5
C/Q 2
IX0.6
C/Q 3
IX0.7
C/Q 4
IB1
IX1.0
Process data IN valid IO-Link-Port 1
IX1.1
Process data IN valid IO-Link-Port 2
IX1.2
Process data IN valid IO-Link-Port 3
IX1.3
Process data IN valid IO-Link-Port 4
IX1.4
Error IO-Link-Port 1
IX1.5
Error IO-Link-Port 2
IX1.6
Error IO-Link-Port 3
IX1.7
Error IO-Link-Port 4
IB2 ...
Process data of the IO-Link device
1)
1) The process data length of the IO-Link devices is adjustable. The mapping
of the IO-Link devices depends on the length of their process data and the
parameter settings.
–
DI X:
Status DI on channel X.
–
C/Q X:
Status C/Q on channel X.
–
Process data IN valid channel X:
Process input data
of the IO-Link devices at IO-Link port X valid.
–
Error channel X:
Error on channel X.
– Process input data of the IO-Link devices:
8.3 Process output data
Process data outputs UR20-4COM-IO-LINK
Byte
Bit
Description
OB0
OX0.0
DO 1
OX0.1
DO 2
OX0.2
DO 3
OX0.3
DO 4
OX0.4
reserved
OX0.5
reserved
OX0.6
reserved
OX0.7
reserved
OB1
OX1.0
Process data OUT valid IO-Link-Port 1
OX1.1
Process data OUT valid IO-Link-Port 2
OX1.2
Process data OUT valid IO-Link-Port 3
OX1.3
Process data OUT valid IO-Link-Port 4
OX1.4
reserved
OX1.5
reserved
OX1.6
reserved
OX1.7
reserved
OB2 ...
Process data of the IO-Link device
1)
1) The process data length of the IO-Link devices is adjustable. The mapping
of the IO-Link devices depends on the length of their process data and the
parameter settings.
–
DO X:
Control C/Q on channel X in DI operation mode.
–
Process data OUT valid channel X:
Process output
data of the IO-Link devices on channel X valid.
– Process output data of the IO-Link devices:
Содержание UR20 Series
Страница 1: ...Remote I O System u remote UR20 Communication module UR20 4COM IO LINK Manual Let s connect...
Страница 8: ...8 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 10: ...10 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 20: ...20 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 48: ...48 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 54: ...54 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...