6 Commissioning
| Reading and writing data objects on IO-Link devices
36
2547720000/03/09.2019
Manual Communication module UR20-4COM-IO-LINK
Addresses for acyclic accesses
Acyclic write access: Addressing the requests (.req)
Protocol
Address
PROFIBUS
227 or 255
PROFINET
227 (0x00E3)
CANopen
0x2200:0
MODBUS-TCP
0x2C00 - 2C7F
EtherCAT
0x4020:1
Ethernet/IP
Class 0x64, Instance 1, Attribute 0x78
DeviceNet
Class 0x64, Instance 1, Attribute 0x78
POWERLINK
0x2200:0
Acyclic read access: Addressing the responses (.res)
Protocol
Address
PROFIBUS
227 or 255
PROFINET
227 (0x00E3)
CANopen
0x2201:0
MODBUS-TCP
0x2D00 - 2D7F
EtherCAT
0x4020:2
Ethernet/IP
Class 0x64, Instance 1, Attribute 0x78
DeviceNet
Class 0x64, Instance 1, Attribute 0x78
POWERLINK
0x2201:0
IO-Link Call
IO-Link data objects and IO-Link port functions are accessed
via IO-Link Call.
With PROFIBUS and PROFINET, you can use the
function block “IO_LINK_CALL” or “IO_LINK_DE-
IO-Link Call: Request
Data object
Length
[bytes] Description
Example
Length
1)
1
Total length in bytes
0x0A
Slot
1)
1
Slot IO-Link master
0x01
Ext. Function Number
2)
1
0x08 (fixed)
0x08
Port
1
Number of the IO-Link port (0x01 ...0x04) 0x02
FI index
2
65098 (0xFE4A)
0xFE4A
Control
1
Write (0x02), Read (0x03)
0x02
IOL index
2
IO-Link device index (0x0000 ... 0xFFFF) 0x0050
IOL subindex
1
IO-Link device data or port function
0x00
IOL data object
0 ... 232 Data for write access
0x42
1) Not for PROFIBUS and PROFINET
2) Not for PROFIBUS and PROFINET
IO-Link Call: Response
Data object
Length
[bytes] Description
Example
Length
1)
1
Total length in bytes
0x0A
Slot
1)
1
Slot IO-Link master
0x01
Ext. Function Number
2)
1
0x08 (fixed)
0x08
Port
1
Number of the IO-Link port (0x01 ...0x04) 0x02
FI index
2
65098 (0xFE4A)
0xFE4A
Status
1
PROFIBUS/PROFINET:
Done (0x00), IDLE (0x01), Error (0x80)
Other fieldbus systems:
Error (0x00), DONE (0x01), Busy (0x02)
0x01
Control response
1)
1
Write (0x02), Read (0x03)
0x02
IOL index
2
IO-Link device index (0x0000 ... 0xFFFF) 0x0050
IOL subindex
1
IO-Link device data or port function
0x00
IOL data object
0 ... 232
Read access: Data
Write access: –
Error incident: error code
–
1) Not for PROFIBUS and PROFINET
2) Not for PROFIBUS and PROFINET
Содержание UR20 Series
Страница 1: ...Remote I O System u remote UR20 Communication module UR20 4COM IO LINK Manual Let s connect...
Страница 8: ...8 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 10: ...10 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 20: ...20 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 48: ...48 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 54: ...54 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...