6 Commissioning
| Commissioning with TwinCAT (EtherCAT)
29
Manual Communication module UR20-4COM-IO-LINK
2547720000/03/09.2019
6.6 Commissioning with TwinCAT (EtherCAT)
Installing the device description files
▶
Before starting TwinCAT, copy the ESI files to the Twin-
CAT installation folder, e.g. C:\TwinCAT\3.1\Config\Io\
EtherCAT.
Existing folder structures in the ESI files must remain un
-
changed when copying.
After starting TwinCAT 3, the devices from the device de
-
scription files are available in the hardware catalogue.
Integrating IO-Link master with TwinCAT 3
▶
Start TwinCAT 3.
▶
Create a new project or open an existing project.
▶
Establish an online connection to the EtherCAT master.
▶
Switch to
Solution Explorer
.
▶
Right-click
I/O
.
▶
Select
Scan
... and follow the configuration wizard.
All the EtherCAT slaves available on the network are added.
IO-Link master in Solution Explorer
Parameterising IO-Link port with TwinCAT
The IO-Link ports are parameterised via the parameters of
the IO-Link master. An overview of all parameters can be
▶
In the
Editor
window of the coupler, switch to
Startup
.
The current parameter setting is displayed.
You can edit the parameter setting.
▶
Double-click the parameter you want to edit.
The
Edit
dialogue box is opened.
Editing module parameters with TwinCAT
▶
Change the value in the
Data
text field.
▶
Click
OK
.
▶
Use this method to edit all of the parameters that you
would like to change.
All settings only take effect once they have been
loaded into the component.
Содержание UR20 Series
Страница 1: ...Remote I O System u remote UR20 Communication module UR20 4COM IO LINK Manual Let s connect...
Страница 8: ...8 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 10: ...10 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 20: ...20 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 48: ...48 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 54: ...54 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...