6 Commissioning
| Commissioning with the SIMATIC Manager (PROFINET)
25
Manual Communication module UR20-4COM-IO-LINK
2547720000/03/09.2019
6.4 Commissioning with the SIMATIC Manager
(PROFINET)
Installing the device description files
Projects must not be open in the hardware
configuration tool while the files are being
installed!
▶
Close any open projects before installing the
device description files!
▶
In the hardware configuration tool, open
Installing
Extras / GSD files
▶
Select the directory in which you have stored the device
description files.
The available files are displayed.
Selecting the GSD(-ML) file
▶
Select the files that you would like to install.
▶
Click
Install
.
▶
When the installation is complete, click
Close
.
▶
Update the device catalogue via
Extras / Update cata-
logue
.
The devices associated with the current device description
file are now listed in the device catalogue.
Integrating IO-Link master with SIMATIC Manager
▶
Start SIMATIC Manager.
▶
Create a new project or open an existing project.
▶
Configure the controller and the network as usual.
▶
Add the appropriate u-remote fieldbus coupler to the sub-
net.
▶
In the hardware configuration tool, click the icon for the
fieldbus coupler.
The module list is displayed in the lower part of the window.
▶
In the module list, click the slot to which you want to add
the IO-Link master.
The device description files support various configura
-
tions for the UR20-4COM-IO-LINK module. The configu
-
rations differ only in the length of the process data for the
IO-Link devices connected, e.g. 16 bytes input data and
16 bytes output data for IO-Link devices for the configuration
UR20-4COM-IOL-16BYTE-INOUT.
Select module with the appropriate process data length
▶
Determine the required process data length of the
IO-Link master, by adding the length of the input data and
output data of the IO-Link devices connected.
▶
In the device catalogue, select the UR20-4COM-IO-LINK
module with a process data length greater than or equal
to the required length.
▶
Double-click the module, or drag it into the module list.
The module is displayed in the module list.
Содержание UR20 Series
Страница 1: ...Remote I O System u remote UR20 Communication module UR20 4COM IO LINK Manual Let s connect...
Страница 8: ...8 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 10: ...10 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 20: ...20 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 48: ...48 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 54: ...54 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...