6 Commissioning
| Commissioning with Automation Studio (POWERLINK)
34
2547720000/03/09.2019
Manual Communication module UR20-4COM-IO-LINK
Restarting the coupler
▶
In the
Physical View
, right-click the module.
▶
Click
Configuration
in the context menu.
The list of all parameters is displayed.
▶
Determine the required process data length of the
IO-Link master, by adding the length of the input data and
output data of the connected IO-Link devices.
▶
Set the “Process data length input” parameter of the
IO-Link master to the required value.
▶
Set the “Process data length input” parameter of the
IO-Link master to the required value.
All settings only take effect once they have been
loaded into the component.
Parameterising IO-Link port with Automation Studio
The IO-Link ports are parameterised via the parameters of
the IO-Link master. An overview of all parameters can be
▶
In the
Physical View
, right-click the module.
▶
In the context menu, click
Configuration
.
The list of all parameters is displayed.
Editing module parameters
▶
Click the parameter that you would like to change and
amend the setting as required.
▶
Use this method to edit all of the parameters that you
would like to change.
All settings only take effect once they have been
loaded into the component.
Integrating IO-Link device with Automation Studio
An IO-Link device is integrated using the appropriate parame-
terisation of the associated IO-Link port.
▶
In the
Physical View
, right-click the module.
▶
In the context menu, click
Configuration
.
The list of all parameters is displayed.
▶
Set the “Operating mode” parameter of the IO-Link port to
the value “IO-Link”.
▶
Set the “Process data length input” parameter of the
IO-Link port to the value “auto (default)”.
▶
Set the “Process data length output” parameter of the
IO-Link port to the value “auto (default)”.
▶
Change the other parameters as required.
All settings only take effect once they have been
loaded into the component.
Содержание UR20 Series
Страница 1: ...Remote I O System u remote UR20 Communication module UR20 4COM IO LINK Manual Let s connect...
Страница 8: ...8 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 10: ...10 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 20: ...20 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 48: ...48 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 54: ...54 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...