4 Module description
| Technical data
16
2547720000/03/09.2019
Manual Communication module UR20-4COM-IO-LINK
UR20-4COM-IO-Link
Flammability rating UL 94
V-0
Temperature data
Operation
-20 °C
...
+60 °C / - 4 ... +140 °F
Storage, transport
-40 °C
...
+85 °C / - 40 ... +185 °F
Humidity
Operation, storage, transport
5 % to 95 %, non-condensing as per IEC 61131-2
Air pressure
Operation
2)
≥ 795 hPa (altitude ≤ 2000 m) as per IEC 61131-2
Storage, transport
≥ 700 hPa (altitude ≤ 3000 m) as per IEC 61131-2
Potential isolation
Test voltage
500 V DC field/system (as per EN 60079-15:2010)
Pollution severity level
2 (as per DIN EN 60664-1:2008)
Overvoltage category
II (as per DIN EN 50178)
Vibration resistance
5 Hz ≤ f ≤ 8.4 Hz: 3.5-mm amplitude as per IEC 60068-2-6
8.4 Hz ≤ f ≤ 150 Hz: 1-g acceleration as per IEC 60068-2-6
Shock resistance
15 g over 11 ms, half sinewave, as per IEC 60068-2-27
Approvals and standards
cULus
UL 61010
Potentially explosive atmosphere Zone 2
ATEX Directive 2014/34/EU
EMC
IEC 61131-9
Explosion protection
IEC 60079-0:2012, IEC 60079-15:2010, EN 60079-0:2012,
EN 60079-15:2010
PLC
IEC 61131-2, IEC 61131-9
1) If C/Q is used as digital input, the connected device shall only be supplied via the L+ and L- connections of the respective channel.
2) Higher altitudes are possible when particular deratings are considered. Please contact your responsible Weidmüller company as needed.
Содержание UR20 Series
Страница 1: ...Remote I O System u remote UR20 Communication module UR20 4COM IO LINK Manual Let s connect...
Страница 8: ...8 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 10: ...10 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 20: ...20 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 48: ...48 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 54: ...54 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...