4 Module description
| Technical data
15
Manual Communication module UR20-4COM-IO-LINK
2547720000/03/09.2019
4.5 Technical data
UR20-4COM-IO-Link
System data
Data (coupler dependent)
Interface
u-remote system bus
System bus transfer rate
48 MBit/s
Digital inputs
Number
4
Sensor types
Typ 1 and Typ 3 acc. IEC 61131-2
Low input voltage
< 5 V
High input voltage
> 11 V
IO-Link interfaces
Number
4
Type
IO-Link as per IEC 61131-9
Transfer rate
4,8 kBaud / 38,4 kBaud / 230,4 kBaud, depending on the connected IO-Link device
Output current C/Q (in DO mode)
0,1 A
Input type C/Q (in DI mode)
1)
Typ 1 and Typ 3 acc. IEC 61131-2
Output current L+
0.5 A per channel, total max. 2 A
Line break detection
yes
Short-circuit-proof
yes
Module diagnosis
yes
Individual channel diagnosis
yes
Supply
Supply voltage
24 V DC +20 %/-15 %
Current consumption from system current path I
SYS
8 mA
Current consumption from input current path I
IN
25 mA + sensor supply
General data
Type of connection
“PUSH IN”
Single-wired, fine-wired
Conductor cross-section 0.14 – 1.5 mm
2
(AWG 16 – 26)
Dimensions
Height
120.0 mm / 4.72" (with release lever: 128.0 mm / 5.04")
Width
11.5 mm / 0.45"
Depth
76.0 mm / 2.99"
Weight (operational status)
88 g
Protection class (IEC 60529)
IP 20
1) If C/Q is used as digital input, the connected device shall only be supplied via the L+ and L- connections of the respective channel.
2) Higher altitudes are possible when particular deratings are considered. Please contact your responsible Weidmüller company as needed.
Содержание UR20 Series
Страница 1: ...Remote I O System u remote UR20 Communication module UR20 4COM IO LINK Manual Let s connect...
Страница 8: ...8 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 10: ...10 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 20: ...20 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 48: ...48 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 54: ...54 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...