6 Commissioning
| Commissioning with Studio 5000(Ethernet/IP)
31
Manual Communication module UR20-4COM-IO-LINK
2547720000/03/09.2019
Change the length of the input data for the module:
▶
Select the service code “Set Single Attribute” (10)
▶
Set the object address parameter as hexadecimal num-
bers.
–
Class: 67 (module parameters)
–
Instance: slot of the UR20-4COM-IO-LINK module
–
Attribute: 65 (length of the input data)
▶
In the drop-down list
Transmit data size
,
select
Byte
.
▶
Determine the required length of the input data of the
UR20-4COM-IO-LINK module by adding the length of the
input data of the connected IO-Link devices as well as
2 status bytes for the module.
▶
In the text field
Data sent to the device
, enter the
determined value as a hexadecimal number.
▶
Click
Execute
to trigger the transaction.
Changing the length of the input data for the module
Change the length of the output data for the module:
▶
Select the service code “Set Single Attribute” (10)
▶
Set the object address parameter as hexadecimal num-
bers.
–
Class: 67 (module parameters)
–
Instance: slot of the UR20-4COM-IO-LINK module
–
Attribute: 66 (length of output data)
▶
In the drop-down list
Transmit data size
,
select
Byte
.
▶
Determine the required length of the output data of the
UR20-4COM-IO-LINK module by adding the length of the
output data of the connected IO-Link devices as well as
2 control bytes for the module.
▶
In the text field
Data sent to the device
, enter the
determined value as a hexadecimal number.
▶
Click
Execute
to trigger the transaction.
Changing the length of the output data for the module
Save the module parameters in the coupler:
▶
Select the service code “Set Single Attribute” (10)
▶
Set the object address parameter as hexadecimal num-
bers.
–
Class: 64 (gateway)
–
Instance: 1
–
Attribute: 6E (save/restore module parameters)
▶
In the drop-down list
Transmit data size
, select
Double
(4 byte)
.
▶
In the text field
Data sent to the device
, enter
“45564153” (“SAVE”, ASCII-coded, Intel format).
▶
Click
Execute
to trigger the transaction.
Saving the module parameters in the coupler
Содержание UR20 Series
Страница 1: ...Remote I O System u remote UR20 Communication module UR20 4COM IO LINK Manual Let s connect...
Страница 8: ...8 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 10: ...10 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 20: ...20 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 48: ...48 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Страница 54: ...54 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...