Watlow PM LEGACY™ Limit Controller
•
81
•
Chapter 7 Factory Page
Factory Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative Ad-
dress
CIP
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
In-
dex
Param-
eter
ID
Data
Type
and Ac-
cess **
iP.A4
ip.A4
Diagnostics
IP Actual Ad-
dress Part 4
Actual IP address
of this module.
Note:
Although it ap-
pears as if this
can be changed
here, this is a read
only parameter.
Go to Setup Page
and then the Com
Menu to change.
0 to 255
- - - -
- - - -
- - - -
- -
- -
17017 R
CAL
FCty
Calibration Menu
ЛЏu
Mv
Calibration
Electrical Mea-
surement
Read the raw
electrical value
for this input in
the units cor-
responding to
the Sensor Type
(Setup Page, An-
alog Input Menu)
setting.
-3.4e38 to 3.4e38
- - - -
Instance 1
Map 1Map 2
400
400
0x68
(104)
1
0x15
(21)
- -
- -
4021
float
R
ELi.o
ELi.o
Calibration
Electrical Input
Offset
Change this val-
ue to calibrate
the low end of
the input range.
-1,999.000 to
9,999.000
0.0
Instance 1
Map 1Map 2
378
378
0x68
(104)
1
0x0A
(10)
- -
- -
4010
float
RWES
ELi.S
ELi.S
Calibration
Electrical Input
Slope
Adjust this value
to calibrate the
slope of the in-
put value.
-1,999.000 to
9,999.000
1.0
Instance 1
Map 1Map 2
380
380
0x68
(104)
1
0xB
(11)
- -
- -
4011
float
RWES
** R: Read, W: Write, E: EEPROM, S: User Set