Watlow PM LEGACY™ Limit Controller
•
55
•
Chapter 6 Setup Page
Setup Page
Display Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
fn
Fn
Digital Output (5 to 6)
Function
Select what function
will drive this output.
off
Off (62)
aLЛЏ
Alarm (6)
Off
Instance 5
Map 1 Map 2
1008 1128
Offset to next
instance (Map
1 & Map 2)
30
0x 6A
(106)
5 to 6
5
83
6005
uint
RWES
fi
Fi
Digital Output (5 to 6)
Output Function In-
stance
Set the instance of
the function selected
above.
1 to 4
Note:
Modbus Map 1
has instances 5
through 8 only
1
Instance 5
Map 1 Map 2
1010 1130
Offset to next
instance (Map
1 & Map 2)
30
0x6A
(106)
5 to 6
6
84
6006
uint
RWES
LEu
LEv
Digital Input (5 to 6)
Active Level
Select which action
will be interpreted as a
true state.
high
High (37)
LoФІ
Low (53)
High
Instance 5
Map 1 Map 2
1320 1560
Offset to next
instance (Map
1 & Map 2)
20
0x6E
(110)
5 to 6
1
137
10001 uint
RW
Fn
Fn
Digital Input (5 to 6)
Action Function
Select the function
that will be triggered
by a true state for Dig-
ital Inputs 5 to 6.
nonE
None (61)
F.AL
Force Alarm
to occur, level
triggered (218)
AoF
Control
Loops Off and
Alarms to Non-
alarm State, level
triggered (220)
SiL
Silence
Alarms, edge
triggered (108)
ALЛЏ
Alarm Re-
set, edge trig-
gered (6)
P.LoC
Keypad
Lockout, level
triggered (217)
usr.r
User Set
Restore, edge
triggered (227)
None
Instance 5
Map 1 Map 2
1324 1564
Offset to next
instance (Map
1 & Map 2)
20
0x6E
(110)
5 to 6
3
138
10003 uint
RWES