Watlow PM LEGACY™ Limit Controller
•
52
•
Chapter 6 Setup Page
Setup Page
Display Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
s.Lo
S.Lo
Analog Input
Scale Low
Set the low scale for
process inputs. This
value, in millivolts,
volts or milliamps,
will correspond to the
Range Low output of
this function block.
-100.00 to
100.00
0.0
Instance 1
Map 1 Map 2
388
388
0x68
(104)
1
0xF (15)
6
4015
float
RWES
s.hi
S.hi
Analog Input
Scale High
Set the high scale for
process inputs. This
value, in millivolts,
volts or milliamperes,
will correspond to the
Range High output of
this function block.
-100.00 to
100.00
20.0
Instance 1
Map 1 Map 2
390
390
0x68
(104)
1
0x10
(16)
7
4016
float
RWES
r.Lo
r.Lo
Analog Input
Range Low
Set the low range for
this function block's
output.
-1,999.000 to
9,999.000
0.0
Instance 1
Map 1 Map 2
392
392
0x68
(104)
1
0x11
(17)
8
4017
float
RWES
r.hi
r.hi
Analog Input
Range High
Set the high range for
this function block's
output.
-1,999.000 to
9,999.000
9,999
Instance 1
Map 1 Map 2
394
394
0x68
(104)
1
0x12
(18)
9
4018
float
RWES
p.EE
P.EE
Analog Input
Process Error Enable
Turn the Process Error
Low feature on or off.
off
Off (62)
LoФІ
Low (53)
Off
Instance 1
Map 1 Map 2
418
418
0x68
(104)
1
0x1E
(30)
10
4030
uint
RWES
p.EL
P.EL
Analog Input
Process Error Low
Value
If the process value
drops below this value,
it will trigger an input
error.
-100.00 to
100.00
0.0
Instance 1
Map 1 Map 2
420
420
0x68
(104)
1
0x1F
(31)
11
4031
float
RWES
** R: Read, W: Write, E: EEPROM, S: User Set