Watlow PM LEGACY™ Limit Controller
•
76
•
Chapter 7 Factory Page
Factory Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative Ad-
dress
CIP
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
In-
dex
Param-
eter
ID
Data
Type
and Ac-
cess **
iid
iid
Custom (1 to 20)
Instance ID
Select which
instance of the
parameter will be
selected.
1 to 4
- - - -
- - - -
- -
- -
14003 uint
RWES
LoC
FCty
Lock Menu
LoC.o
LoC.o
Security Setting
Operations Page
Change the se-
curity level of
the Operations
Page.
1 to 3
2
Instance 1
Map 1 Map 2
1832 2302
0x67
(103)
1
2
- -
- -
3002
uint
RWE
pas.E
LoC.P
Security Setting
Password En-
able
Set to On to re-
quire a password
for menu chang-
es.
off
Off
on
On
Off
- - - -
- - - -
- -
- -
3009
uint
RWE
rLoC
rLoC
Security Setting
Read Lock
Set the read se-
curity clearance
level. The user can
access the select-
ed level and all
lower levels.
If the Set Lock-
out Security level
is higher than
the Read Lock-
out Security, the
Read Lockout
Security level
takes priority.
1 to 5
5
Instance 1
Map 1 Map 2
1848 2318
0x67
(103)
1
0x0A
(10)
- -
- -
3010
uint
RWE
** R: Read, W: Write, E: EEPROM, S: User Set
Содержание PM LEGACY PM3
Страница 119: ...Watlow PM LEGACY Limit Controller 119 Appendix...