Chapter 6 Setup Page
Setup Page
Display Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
Fi
Fi
Digital Input (5 to 6)
Function Instance
Select which Digital
Input will be triggered
by a true state.
0 to 40
0
Instance 5
Map 1 Map 2
1326 1566
Offset to next
instance (Map
1 & Map 2)
20
0x6E
(110)
5 to 6
4
139
10004 uint
RWES
LiЛЏ
sEt
Limit Menu
L.sd
L.Sd
Limit
Sides
Select which side or
sides of the process
value will be moni-
tored.
both
Both (13)
high
High (37)
LoФІ
Low (53)
Both
Instance 1
Map 1 Map 2
688
728
0x70
(112)
1
5
40
12005 uint
RWES
L.hy
L.hy
Limit
Hysteresis
Set the hysteresis for
the limit function. This
determines how far
into the safe range the
process value must
move before the limit
can be cleared.
0.001 to
9,999.000°F or
units
0.001 to
5,555.000°C
3.0°F or
units
2.0°C
Instance 1
Map 1 Map 2
682
722
0x70
(112)
1
2
41
12002 float
RWES
sp.Lh
SP.Lh
Limit
Maximum Set Point
Set the high end of the
limit set point range.
-1,999.000 to
9,999.000
9,999.000
Instance 1
Map 1 Map 2
696
736
0x70
(112)
1
9
42
12009 float
RWES
sp.LL
SP.LL
Limit
Minimum Set Point
Set the low end of the
limit set point range.
-1,999.000 to
9,999.000
-1,999.000
Instance 1
Map 1 Map 2
698
738
0x70
(112)
1
0xA (10)
43
12010 float
RWES
Lh.s
Lh.S
Limit
High Limit Set Point
Set the high process
value that will trigger
the limit.
-1,999.000 to
9,999.000°F or
units
-1,128.000 to
5,537.000°C
0.0°F or
units
-18.0°C
Instance 1
Map 1 Map 2
686
726
0x70
(112)
1
4
39
12004 float
RWES
** R: Read, W: Write, E: EEPROM, S: User Set