Using Lockout Method 1 (Read and Set Lock)
All Pages have security levels assigned where two of those cannot be changed (Home and Setup).
Defaults (factory settings) for each are shown below:
- Home Page = 1
- Operations Page = 2 (changeable to 1, 2 or 3)
- Setup Page = 4
- Profiling Page = 3 (changeable to 1, 2 or 3)
- Factory Page = 5*
* The Factory Page is always visible where all menus within it may or may not be visible/writable. For
further detail see table “Factory Page Menus”.
The table below represents the various levels of lockout for the Set Lockout Security prompt
sLoC
and the Read Lockout Security prompt
rLoC
. Looking at the table, “Y” equates to yes (can write/read)
where “N” equates to no (cannot write/read). The colored cells simply differentiate one level from the
next while also showing the level where read/write is enabled. As stated previously, the Set Lockout
has 6 levels (0 to 5) of security where the Read Lockout has 5 (1 to 5). Therefore, level “0” applies to
Set Lockout only.
Lockout Security
sLoC
and
rLoC
Pages
Security Level
0
1
2
3
4
5
Home Page (cannot be changed)
N
Y
Y
Y
Y
Y
Operations Page
N
N
Y
Y
Y
Y
Setup Page (cannot be changed)
N
N
N
N
Y
Y
Factory Page
Y
Y
Y
Y
Y
Y
Being able to change the page security level for the Operations and Profile pages allows a user to
give access to the Profile Page while locking out the Operations Page. The following example shows
how the Lockout feature may be used to accomplish this:
Changing Security Levels:
1. From the Home Page, press and hold the Reset Key and the Advance Key for approximately six sec-
onds.
CUst
will appear in the upper display and
fCty
will appear in the lower display.
2. Press the Up Key
until
LoC
appears in the upper display and
fCty
will appear in the lower dis-
play.
3. Press the Advance Key until Lock Operations prompt
LoC.o
appears in the bottom display.
4. Press the Up Key to change the default value from
2
to
3
.
5. Press the Advance Key again and change the Lock Profiling prompt
LoC.p
appears in the bottom dis-
play.
6. Press the Down
Key
to change the default value from
3
to
2
.
7. Press the Advance Key until Read Lock
rLoC
appears in the bottom display.
8. Press the Down
Key
to change the default value from
5
to
2
.
9. Press the Advance Key until Set Lock
sLoC
appears in the bottom display.
10. Press the Down
Key
to change the default value from
5
to
4
.
With the above settings, the Home Page and the Profiling Page can be accessed, and all writable pa-
rameters can be written to. Due to the Read lock setting of 2, all pages with security
levels greater
than 2 will be locked out (inaccessible).