Watlow PM LEGACY™ Limit Controller
•
51
•
Chapter 6 Setup Page
Setup Page
Display Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
Ai
sEt
Analog Input Menu
sEn
SEn
Analog Input
Sensor Type
Set the analog sensor
type to match the de-
vice wired to this input.
Note:
There is no open
sensor protection for
process inputs.
off
Off (62)
tC
Thermocouple
(95)
ЛЏu
Millivolts (56)
voLt
Volts dc
(104)
ЛЏa
Milliamps dc
(112)
r0.1H
RTD 100 Ω
(113)
r1.0H
RTD 1,000
Ω (114)
pot
Potentiome-
ter 1 kΩ (155)
thEr
Thermistor
(229)
Thermo-
couple or
Thermis-
tor
Instance 1
Map 1 Map 2
368 368
0x68
(104)
1
5
3
4005
uint
RWES
Lin
Lin
Analog Input
TC Linearization
Set the linearization to
match the thermocou-
ple wired to this input.
b
B (11)
H
K (48)
C
C (15)
n
N (58)
d
D (23)
r
R (80)
E
E (26)
s
S (84)
f
F (30)
t
T (93)
J
J (46)
J
Instance 1
Map 1 Map 2
370 370
0x68
(104)
1
6
4
4006
uint
RWES
rt.L
rt.L
Analog Input
RTD Leads
Set to match the
number of leads on
the RTD wired to this
input.
2
2 (1)
3
3 (2)
2
Instance 1
Map 1 Map 2
372 372
0x68
(104)
1
7
- - - - 4007
uint
RWES
Unit
Unit
Analog Input
Units
Set the type of units
the sensor will mea-
sure.
a.tp
Absolute
Temperature
(1540)
rh
Relative Hu-
midity (1538)
pro
Process (75)
PФІr
Power (73)
Process
Instance 1
Map 1 Map 2
- - - - 442
0x68
(104)
1
0x2A
(42)
5
4042
uint
RWES
** R: Read, W: Write, E: EEPROM, S: User Set