Watlow PM LEGACY™ Limit Controller
•
77
•
Chapter 7 Factory Page
Factory Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative Ad-
dress
CIP
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
In-
dex
Param-
eter
ID
Data
Type
and Ac-
cess **
SLoC
SLoC
Security Setting
Write Security
Set the write se-
curity clearance
level. The user
can access the
selected level
and all lower
levels.
If the Set Lockout
Security level is
higher than the
Read Lockout
Security, the
Read Lockout
Security level
takes priority.
0 to 5
5
Instance 1
Map 1 Map 2
1844 2314
0x67
(103)
1
0x0B
(11)
- -
- -
3011
uint
RWE
LoC.L
LoC.L
Security Setting
Locked Access
Level
Determines user
level menu visi-
bility when Pass-
word Enable is
set to on. See
Features section
under Password
Security.
1 to 5
5
- - - -
- - - -
- -
- -
3016
uint
RWE
roLL
roLL
Security Setting
Rolling Pass-
word
When power is
cycled a new
Public Key will
be displayed and
User Password
changes.
off
Off
on
On
Off
- - - -
- - - -
- -
- -
3019
uint
RWE
pas.u
PAS.u
Security Setting
User Password
Used to acquire
access to menus
made available
through the
Locked Access
Level setting.
10 to 999
63
- - - -
- - - -
- -
- -
3017
uint
RWE
** R: Read, W: Write, E: EEPROM, S: User Set
Содержание PM LEGACY PM3