Watlow PM LEGACY™ Limit Controller
•
53
•
Chapter 6 Setup Page
Setup Page
Display Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
t.C
t.C
Analog Input
Thermistor Curve
Select a curve to apply
to the thermistor input.
a
Curve A (1451)
b
Curve B (1452)
C
Curve C (1453)
CUst
Custom
(180)
Curve A
Instance 1
Map 1 Map 2
434
434
0x68
(104)
1
0x26
(38)
- - - - 4038
uint
RWES
r.r
r.r
Analog Input
Resistance Range
Set the maximum re-
sistance of the therm-
istor input.
5
5K (1448)
10
10K (1360)
20
20K (1361)
40
40K (1449)
40K
Instance 1
Map 1 Map 2
432
432
0x68
(104)
1
0x25
(37)
- - - - 4037
uint
RWES
fiL
FiL
Analog Input
Filter
Filtering smooths out
the process signal to
both the display and
the input. Increase the
time to increase filter-
ing.
0.0 to 60.0 sec-
onds
Note:
Filter does not
apply to the Limit
sensor but does
apply to all other
functions.
0.5
Instance 1
Map 1 Map 2
386 386
0x68
(104)
1
0xE (14)
12
4014
float
RWES
i.Er
i.Er
Analog Input
Input Error Latching
Turn input error latch-
ing on or off. If latching
is on, errors must be
manually cleared.
off
Off (62)
on
On (63)
Off
Instance 1
Map 1 Map 2
414
414
0x68
(104)
1
0x1C
(28)
- - - - 4028
uint
RWES
dEC
dEC
Analog Input
Display Precision
Set the precision of the
displayed value.
0
Whole (105)
0.0
Tenths (94)
0.00
Hundredths
(40)
0.000
Thou-
sandths (96)
Whole
Instance 1
Map 1 Map 2
398
398
0x68
(104)
1
0x14
(20)
- - - - 4020
uint
RWES
i.Ca
i.CA
Analog Input
Calibration Offset
Off-
set the input reading
to compensate for lead
wire resistance or oth-
er factors that cause
the input reading to
vary from the actual
process value.
-1,999.000 to
9,999.000°F or
units
-1,110.555 to
5,555.000°C
0.0
Instance 1
Map 1 Map 2
382
382
0x68
(104)
1
0xC (12)
2
4012
float
RWES
** R: Read, W: Write, E: EEPROM, S: User Set