Watlow PM LEGACY™ Limit Controller
•
61
•
Chapter 6 Setup Page
Setup Page
Display Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
A.hy
A.hy
Alarm (1 to 4)
Hysteresis
Set the hysteresis for
an alarm. This deter-
mines how far into the
safe region the pro-
cess value needs to
move before the alarm
can be cleared.
0.001 to
9,999.000°F or
units
0.001 to
5,555.000°C
1.0°F or
units
1.0°C
Instance 1
Map 1Map 2
1484 1884
Offset to next
instance (Map
1 50,
Map 2 +60)
0x6D
(109)
1 to 4
3
24
9003 float
RWES
A.Lg
A.Lg
Alarm (1 to 4)
Logic
Selec
t what the out-
put condition will be
during the alarm state.
AL.C
Energize on
alarm (17)
AL.o
De-energize
on alarm (66)
Close On
Alarm
Instance 1
Map 1Map 2
1488 1888
Offset to next
instance (Map
1 +50, Map 2
+60)
0x6D
(109)
1 to 4
5
25
9005 uint
RWES
A.Sd
A.Sd
Alarm (1 to 4)
Sides
Select which side or
sides will trigger this
alarm.
both
Both (13)
high
High (37)
LoФІ
Low (53)
Both
Instance 1
Map 1Map 2
1486 1886
Offset to next
instance (Map
1 +50, Map 2
+60)
0x6D
(109)
1 to 4
4
26
9004 uint
RWES
A.Lo
A.Lo
Alarm (1 to 4)
Low Set Point
Set the process value
that will trigger a low
alarm.
-1,999.000 to
9,999.000°F or
units
-1,128.000 to
5,537.000°C
32.0°F
or units
0.0°C
Instance 1
Map 1Map 2
1482 1882
Offset to
next instance
(Map 1 +50,
Map 2 +60)
0x6D
(109)
1 to 4
2
18
9002
float
RWES
A.hi
A.hi
Alarm (1 to 4)
High Set Point
Set the process value
that will trigger a high
alarm.
-1,999.000 to
9,999.000°F or
units
-1,128.000 to
5,537.000°C
300.0°F
or units
150.0°C
Instance 1
Map 1Map 2
1480 1880
Offset to
next instance
(Map 1 +50,
Map 2 +60)
0x6D
(109)
1 to 4
1
19
9001
float
RWES
** R: Read, W: Write, E: EEPROM, S: User Set