Watlow PM LEGACY™ Limit Controller
•
84
•
Chapter 8 Features
How to Change the Controller Model Number
1. Enter Factory Page
FCty
, Calibration Menu
CaL
via front panel by pressing the Reset Key and the
Advance Key together or using PM LEGACY™ Limit Configurator software.
2. Once there, use the Advance Key to navigate to the Part Number
pn
prompt. The top display will
show factory
FCty
indicating the factory model number as shown on the decal located on the
side of the control is currently in effect.
3. Push the Advance Key, Public Key
Co dE
prompt will be displayed and the number
4999
in the top
display.
4. Using the up or down Arrow Keys enter
2501
and push the Advance Key to execute the change.
The controller will reboot and the new controller model number is in effect. All previous settings
are lost and the controller must be reprogrammed for the application. Be sure to label the control-
ler with the new model number for future reference.
Note:
As noted above, when switching from a PM Standard to a PM Express version, optional hardware
(even though installed) may no longer work. Also, all settings will be defaulted to the selected model
when switched.
Note:
After switching the model number to a PM Express this document will no longer apply to the con-
trol. Click on the link that follows to acquire the latest version of the PM LEGACY™ Limit User’s
Guide.
http://www.watlow.com/en/Resources-And-Support/Technical-Library/User-Manuals
Once there, simply enter express in the “Keyword” field to find the appropriate document.
How to Restore Original PM Factory Settings and Model Number
1
. Enter Factory Page
FCty
, Calibration Menu
CaL
via front panel by pressing the Reset Key and the
Advance Key together or using PM LEGACY™ Limit Configurator software.
2. Once there, use the Advance Key to navigate to the Part Number
pn
prompt. The upper display
will show user
USEr
indicating the user’s selected model number is currently in effect.
3. Push the Advance Key where the Public Key
Co dE
prompt will appear in the lower display and the
number
4999
in the upper display.
4. Using the up or down arrow keys
enter
606
and push the Advance Key to execute the
change. The controller will reboot and the new controller model number is in effect. All previous
settings are lost and the controller must be reprogrammed for the application. Be sure to label the
controller with the new model number for future reference.
Note:
When switching from a PM Express back to the original model number all original optional hardware
will again be enabled for use. Also, when executing this step the control will be factory defaulted
back to the original model number (as shown on the side of the control) at zone address 1. This Us-
er’s Guide would once again apply to this control.