Watlow PM LEGACY™ Limit Controller
•
68
•
Chapter 6 Setup Page
Setup Page
Display Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
nU.S
nV.S
Communications (1
or 2)
Non-Volatile Save
If set to Yes all values
written to the control
will be saved in EE-
PROM. The EEPROM
allows for approx-
imately one million
writes.
yEs
Yes (106)
no
No (59)
Yes
Instance 1
Map 1Map 2
2494 2974
0x96
(150)
1
8
198
17051 uint
RWE
no dis-
play
Communications (1
or 2)
Tick
Value increases at
1mS rate.
0 to
4,294,967,295
- - - -
Instance 1
Map 1Map 2
5020 8950
- - - -
- - - - 16006 un-
signed
32-bit
RWE
DeviceNet
Ad.d
Ad.d
Communications (2)
DeviceNet™ Node
Address
Set the DeviceNet™
address for this gate-
way.
0 to 63
63
- - - -
- - - -
- - - - 17052
- - - -
bAUd
bAUd
Communications (2)
DeviceNet™ Baud
Rate
Set the DeviceNet
speed for this gate-
way's communications
to match the speed of
the serial network.
125
125 kb
(1351)
250
250 kb
(1352)
500
500 kb
(1353)
125
- - - -
- - - -
- - - - 17053
- - - -
FC.E
FC.E
Communications (2)
DeviceNet™ Quick
Connect Enable
Allows for immediate
communication with
the scanner upon
power up.
no
No (59)
yES
Yes (106)
No
- - - -
- - - -
- - - - 17054
- - - -
ao.nb
Ao.nb
Communications (2)
CIP Implicit Assem-
bly Output Member
Quantity
1 to 20
20
- - - -
- - - -
- - - - 24009
- - - -
ai.nb
Ai.nb
Communications (2)
CIP Implicit Assembly
Input Member Quan-
tity
1 to 20
20
- - - -
- - - -
- - - - 24010
- - - -
** R: Read, W: Write, E: EEPROM, S: User Set
Содержание PM LEGACY PM3