Watlow PM LEGACY™ Limit Controller
•
73
•
Chapter 6 Setup Page
Setup Page
Display Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
ai.nb
Ai.nb
Communications (2)
EtherNet/IP™ Input
Assembly
When using EtherNet/
IP set the CIP Implicit
Assembly Input Mem-
ber Quantity
1 to 40
40
- - - -
- - - -
- - - - 24010
- - - -
C_F
C_F
Communications (2)
Display Units
Select which scale to
use for temperature
passed over commu-
nications port 2.
F
°F (30)
C
°C (15)
°F
Instance 2
Map 1Map 2
- - - - 2990
0x96
(150)
2
6
199
17050 uint
RWE
nU.S
nV.S
Communications (2)
Non-volatile Save
If set to Yes all values
written to the control
will be saved in EE-
PROM. The EEPROM
allows for approx-
imately one million
writes.
yEs
Yes (106)
no
No (59)
No
Instance 2
Map 1Map 2
2514 2994
96 (150)
2
8
198
17051 uint
RWE
** R: Read, W: Write, E: EEPROM, S: User Set
Содержание PM LEGACY PM3