WAGO I/O System 750
Appendix 223
750-8210/040-000 PFC200; G2; 4ETH; XTR
Manual
Version 1.7.0, valid from FW Version 04.01.10(23)
“BACnet Eventlog” Group
This group lets you select the storage location (SD card/internal flash) for the
event log data.
Table 128
: WBM Page “BACnet Storage Location” – “BACnet Eventlog” Group
Parameter
Meaning
Storage location
Select the storage location for the event log data
here.
Selection is possible only when both storage options
are available.
Internal-Flash
Data will be stored in the controller's
internal memory.
SD-Card
Data will be stored on the SD card.
If “SD card” has been selected and
the card is no longer inserted, this
option is no longer enabled and only
the “internal flash” option can be
selected.