46
Properties
WAGO I/O System 750
750-8210/040-000 PFC200; G2; 4ETH; XTR
Manual
Version 1.7.0, valid from FW Version 04.01.10(23)
4.3.9
Mechanical Environmental Conditions
Table 23: Technical Data
– Mechanical Environmental Conditions
Vibration resistance
Max. 5g
*)
*
Follow the installation instructions
4.3.10
Climatic Environmental Conditions
Table 24: Technical Data
– Climatic Environmental Conditions
Surrounding air temperature, operation
−40 … +70 °C
Vertical mounting position:
−40 … +65 °C
Surrounding air temperature, storage
−40 … +85 °C
Relative humidity
*)
5
… 95 % without condensation
Operating altitude above sea level
without temperature derating
with temperature derating
max.
0
… 2000 m
2000
… 5000 m:
0.5 K per 100 m
5000 m
Pollution degree
2
Protection type
IP20
Resistance to harmful substances
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
Maximum pollutant concentration at
relative humidity < 75 %
SO
2
25 ppm
H
2
S
10 ppm
Special conditions
•
The permissible temperature range
of the connecting cable must be
dimensioned based on the
mounting position and current
intensity, as the temperature of the
terminal connection can be up to
25 °K above the maximum
expected surrounding air
temperature (at 10 A).
*)
Short-term condensation acc. class 3K7 / IEC EN 60721-3-3 permitted, applying
E-DIN 40046-721-3 (except wind-driven precipitation, water and ice formation)