7.4
Grounding
7.4.1
Grounding the DIN Rail
7.4.1.1
Framework Assembly
When setting up the framework, the carrier rail must be screwed together with the
electrically conducting cabinet or housing frame. The framework or the housing
must be grounded. The electrical connection is established via the screw. Thus,
the carrier rail is grounded.
Ensure sufficient grounding is provided!
You must take care to ensure the flawless electrical connection between the
carrier rail and the frame or housing in order to guarantee sufficient grounding.
7.4.1.2
Insulated Assembly
Insulated assembly has been achieved when there is constructively no direct
ohmic contact between the cabinet frame or machine parts and the carrier rail.
Here, the earth ground must be set up via an electrical conductor in accordance
with valid national safety regulations.
Recommendation
The optimal setup is a metallic assembly plate with grounding connection which
is electrically conductive linked to the carrier rail.
The separate grounding of the carrier rail can be easily set up with the aid of the
WAGO ground wire terminals.
Table 44: WAGO Ground Wire Terminals
Order No. Description
283-609
1-conductor ground (earth) terminal block make an automatic
contact to the carrier rail; conductor cross section:
0.2 mm²
… 16 mm
2
Note
: Also order the end and intermediate plate (283-320).