WAGO I/O System 750
Diagnostics 155
750-8210/040-000 PFC200; G2; 4ETH; XTR
Manual
Version 1.7.0, valid from FW Version 04.01.10(23)
Table 66: Error Code 9, Explanation of Blink Codes and Procedures for Troubleshooting
Error
Argument
Cause
Remedy
1
Invalid program
statement
Malfunction of the program sequence:
-
Contact WAGO Support.
2
Stack overflow
Malfunction of the program sequence:
-
Contact WAGO Support.
3
Stack underflow
Malfunction of the program sequence:
-
Contact WAGO Support.
4
Invalid event (NMI)
Malfunction of the program sequence:
-
Contact WAGO Support.
5
Local bus watchdog
has triggered.
For CODESYS V3 applications:
-
Check the system load by IEC tasks
with priorities 1 ... 14 in the runtime
system (see Section “CODESYS V3”
Runtime Environment >
“CODESYS V3 Priorities”).
For C applications:
-
Check the time monitoring settings.