106
Function
Explanation
9.
"Commissioning"
Testing the control characteristics, manual con-
trol over setting parameters and programming
the controller.
10.
"Standard mode"
Starting regular operation
Calling up the commissioning assis-
tant
A
C B
1.
Open the programming unit flap in the
front panel by pressing on the flap.
2.
Starting the system with ON/OFF
switch
A
.
A progress bar "Check System"
appears in the display
3.
Press key 6
C
on the programming
unit whilst the progress bar is filling
from left to right.
Note
During the initial start, all terms appear
in German (delivered condition).
1. Language selection
Press
y
or
x
and confirm with
"OK"
.
2. Safety check
NO
Are you sure?
YES
Safety check
Commissioning
1.
The commissioning assistant starts
with the security check
"Are you
sure?"
2.
Press
"YES"
as confirmation (or
"NO"
to cancel).
3.
After starting the commissioning
assistant, the system progresses
through all 10 steps. Pressing the
standard settings key
B
enables a
program termination at any time. The
commissioning assistant can be
restarted with a power reset.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5368 522 UAE
Содержание Vitocal 300-G BW
Страница 57: ...57 6 1 2 4 3 5 A 5x Installation sequence Opening the heat pump 5368 522 UAE Installation...
Страница 188: ...188 VITOCAL 300 205 025 011 203 202 200 206 207 204 201 010 025 A 026 Parts lists Parts lists type BWC cont 5368 522 UAE...
Страница 194: ...194 VITOCAL 300 205 203 202 200 206 207 204 201 010 026 025 A 025 Parts lists Parts lists type BW cont 5368 522 UAE...
Страница 213: ...213 5368 522 UAE...
Страница 214: ...214 5368 522 UAE...
Страница 215: ...215 5368 522 UAE...