136
No. Affects the following system components
6 A1: Direct heating circuit
M2: Heating circuit with mixer, DHW heating
7 M2: Heating circuit with mixer
M3: Heating circuit with mixer
8 M2: Heating circuit with mixer
M3: Heating circuit with mixer, DHW heating
9 A1: Direct heating circuit
M2: Heating circuit with mixer
M3: Heating circuit with mixer
10 A1: Direct heating circuit
M2: Heating circuit with mixer
M3: Heating circuit with mixer, DHW heating
11 No heating circuit or DHW changeover. Only "Ext. demand" function.
External operating mode changeover effect
Parameter
■ 7012
Details in which operating mode the
components selected under parame-
ter 7011 (see previous section) are oper-
ated after an external operating mode
changeover.
Access
■ "
Device settings
"
■ "
Programming
"
■ "
System definition
"
■
y
to
"Op. mode change eff."
■
l
or
m
Standard setting
2
Setting range
0 to 3
Settings explained:
0 Standby
1 Reduced
2 Standard
3 Fixed value
External operating mode changeover duration
Parameter
■ 7013
Duration of the operating mode change-
over, even if "Party mode" is currently
enabled.
System definition control settings
External operating mode changeover heating…
(cont.)
5368 522 UAE
Содержание Vitocal 300-G BW
Страница 57: ...57 6 1 2 4 3 5 A 5x Installation sequence Opening the heat pump 5368 522 UAE Installation...
Страница 188: ...188 VITOCAL 300 205 025 011 203 202 200 206 207 204 201 010 025 A 026 Parts lists Parts lists type BWC cont 5368 522 UAE...
Страница 194: ...194 VITOCAL 300 205 203 202 200 206 207 204 201 010 026 025 A 025 Parts lists Parts lists type BW cont 5368 522 UAE...
Страница 213: ...213 5368 522 UAE...
Страница 214: ...214 5368 522 UAE...
Страница 215: ...215 5368 522 UAE...