137
Access
■ "
Device settings
"
■ "
Programming
"
■ "
System definition
"
■
y
to
"Op. mode change time"
■
l
or
m
Standard setting
8 h
Setting range
0 to 12 h
Settings explained:
0
No specified duration; change-
over takes place as long as the
changeover contact remains
closed.
1 - 12 Duration of the changeover start-
ing with the activation of the oper-
ating mode changeover.
External demand/mixer OPEN
Parameter
■ 7014
Details how the "Ext. demand" or "Mixer
OPEN" functions should affect the heat
pump.
Access
■ "
Device settings
"
■ "
Programming
"
■ "
System definition
"
■
y
to
"Ext.demand/Miopen"
■
l
or
m
Standard setting
4
Setting range
0 to 7
Note
■ The parameter "Ext. Blocking" takes
higher priority than "External
demand" (see page 138 : Parameter
7015).
■ See also parameter 730C: "Set flow
temperature external demand",
page 155.
No. Function of the following system components
0 M2/M3: Heating circuits with mixer – control mode
No heat demand to the heat pump
1 M2: Heating circuit with mixer – moves into the OPEN position
M3: Heating circuit with mixer – control mode
No heat demand to the heat pump
2 M2: Heating circuit with mixer – control mode
M3: Heating circuit with mixer – moves into the OPEN position
No heat demand to the heat pump
3 M2/M3: Heating circuits with mixer – move into the OPEN position
No heat demand to the heat pump
System definition control settings
External operating mode changeover duration
(cont.)
5368 522 UAE
Service
Содержание Vitocal 300-G BW
Страница 57: ...57 6 1 2 4 3 5 A 5x Installation sequence Opening the heat pump 5368 522 UAE Installation...
Страница 188: ...188 VITOCAL 300 205 025 011 203 202 200 206 207 204 201 010 025 A 026 Parts lists Parts lists type BWC cont 5368 522 UAE...
Страница 194: ...194 VITOCAL 300 205 203 202 200 206 207 204 201 010 026 025 A 025 Parts lists Parts lists type BW cont 5368 522 UAE...
Страница 213: ...213 5368 522 UAE...
Страница 214: ...214 5368 522 UAE...
Страница 215: ...215 5368 522 UAE...