94
Sealing the low tariff connection
A part of the contact shield (mains terminal cover) is used for sealing (see
page 88).
Note
The power supply utility can demand that
the low tariff connection is sealed.
A
B
D
E
C
1.
Separating the smaller cover
panel
C
from the contact shield
A
by breaking along the perfora-
tion
E
.
2.
Fit the contact shield
A
using the
mounting holes
B
in front of the
mains terminals.
3.
Push separated cover panel
C
with
both mounting holes over the 2 studs
and secure it on the studs.
4.
Guide the seal wire through
holes
D
in both studs.
Phase monitor
The phase monitor is used to monitor the mains power supply to the compressor.
Different versions may be used.
Installation sequence
Power supply
(cont.)