165
Parameter
■ 7103
Limiting the flow temperature of the sep-
arate cooling circuit to a minimum
value.
Access
■ "
Device settings
"
■ "
Programming
"
■ "
Cooling
"
■
y
to "
Min. flow temp.
"
■
1
or
!
Standard setting
10 °C
Setting range
1 to 30 °C
Room hook-up slope, separate cooling circuit
Parameter
■ 7104
A room temperature sensor must be
installed for a separate cooling circuit.
For this, the slope (influence) of the room
temperature hook-up can be selected.
The higher the selected value, the
greater the influence of the room tem-
perature.
For example, value 10 means that, at
1 K room temperature deviation, the flow
temperature is modified by 10 K.
See also parameter "Room hook-up
heating circuits" page 162.
Access
■ "
Device settings
"
■ "
Programming
"
■ "
Cooling
"
■
y
to "
Room t hook-up slope
"
■
l
or
m
Standard setting
0
Setting range
0 to 50
Cooling curve level/slope
Parameter
■ 7110 (level)
■ 7111 (level)
Precondition: Cooling function is active.
Cooling control settings
Min. flow temperature
5368 522 UAE
Service