164
Parameter
■ 7100
Determining the function of active cool-
ing.
Access
■ "
Device settings
"
■ "
Programming
"
■ "
Cooling
"
■ "
Cooling
"
■
l
or
m
Standard setting
0
Setting range
0 to 3
Settings explained:
0 No cooling
1 NC-Box without mixer
2 NC-Box with mixer
3 AC-Box
Cooling circuit
Parameter
■ 7101
Determining which circuit (heating circuit
or separate cooling circuit) cooling
affects.
Access
■ "
Device settings
"
■ "
Programming
"
■ "
Cooling
"
■
y
to "
Cooling circuit
"
■
l
or
m
Standard setting
1
Setting range
1 to 4
Settings explained:
1 Cooling in heating circuit 1 (A1)
2 Cooling in the heating circuit 2 (M2)
3 Cooling in heating circuit 3 (M3)
4 Cooling in a separate cooling circuit
Room temperature separate cooling circuit
Parameter
■ 7102
Operating instructions
Cooling control settings
Cooling