138
No. Function of the following system components
4 M2/M3: Heating circuits with mixer – control mode
Heat demand to the heat pump
5 M2: Heating circuit with mixer – moves into the OPEN position
M3: Heating circuit with mixer - control mode
Heat demand to the heat pump
6 M2: Heating circuit with mixer – control mode
M3: Heating circuit with mixer – moves into the OPEN position
Heat demand to the heat pump
7 M2/M3: Heating circuits with mixer – move into the OPEN position
Heat demand to the heat pump
External Blocking/mixer CLOSE
Parameter
■ 7015
Details how the "Ext. Blocking" or "Mixer
CLOSE" functions should affect the heat
pump.
!
Please note
The system frost protection may
no longer be ensured.
Access
■ "
Device settings
"
■ "
Programming
"
■ "
System definition
"
■
y
to
"Ext.blocking/Miclose"
■
l
or
m
Standard setting
4
Setting range
0 to 8
Note
■ The parameter "Ext. Blocking" takes
higher priority than "External
demand".
■ See also parameter 730C: "Set flow
temperature external demand",
page 155.
No. Function to the associated setting
0 M2/M3: Heating circuits with mixer – control mode
No heat pump blocking
1 M2: Heating circuit with mixer – moves into the CLOSE position
M3: Heating circuit with mixer – control mode
No heat pump blocking
System definition control settings
External demand/mixer OPEN
(cont.)
5368 522 UAE
Содержание Vitocal 300-G BW
Страница 57: ...57 6 1 2 4 3 5 A 5x Installation sequence Opening the heat pump 5368 522 UAE Installation...
Страница 188: ...188 VITOCAL 300 205 025 011 203 202 200 206 207 204 201 010 025 A 026 Parts lists Parts lists type BWC cont 5368 522 UAE...
Страница 194: ...194 VITOCAL 300 205 203 202 200 206 207 204 201 010 026 025 A 025 Parts lists Parts lists type BW cont 5368 522 UAE...
Страница 213: ...213 5368 522 UAE...
Страница 214: ...214 5368 522 UAE...
Страница 215: ...215 5368 522 UAE...