The following different mains supplies (if
adjustable) are permissible in the deliv-
ered condition:
Over/undervoltage
15 %
Phase asymmetry
15 %
Switching delay
4 s
The phase monitor switches off (switch-
ing contact opens) if these tolerances
are exceeded.
The phase monitor automatically re-ena-
bles the power supply if the values fall
back to within the specified tolerance
range.
Remove the cause if the relay has
responded. The relay does not need to
be reset.
A
H
B
C
G
F
E
D
D
<>U
A1
Asy
Ph
Rel
A2
L1
L2
L3
14
11
12
<>U
Asy
t
2
4
12
%
15
10
5
%
20
10
6
0.1
A
Over/undervoltage in %
B
Phase asymmetry in %
C
Switching delay in s
D
Contact used in the safety chain (N/
O)
E
Operating display ("Rel")
F
Fault display phase failure/phase
sequence ("Ph")
LEDs explained
■ LED "Rel" illuminates green:
All voltages and the rotating field
(clockwise) are healthy.
■ LED "Ph" illuminates red:
The relay has responded; the rotating
field is anti-clockwise.
■ All LED's off:
One or several phases have dropped
out.
■ LED "<>U" illuminates red:
Incorrect voltage on one/several
phase(s).
■ LED "Asy" illuminates red:
Incorrect voltage on one/several
phase(s).
Installation sequence
Power supply
(cont.)
5368 522 UAE
Installation
Содержание Vitocal 300-G BW
Страница 57: ...57 6 1 2 4 3 5 A 5x Installation sequence Opening the heat pump 5368 522 UAE Installation...
Страница 188: ...188 VITOCAL 300 205 025 011 203 202 200 206 207 204 201 010 025 A 026 Parts lists Parts lists type BWC cont 5368 522 UAE...
Страница 194: ...194 VITOCAL 300 205 203 202 200 206 207 204 201 010 026 025 A 025 Parts lists Parts lists type BW cont 5368 522 UAE...
Страница 213: ...213 5368 522 UAE...
Страница 214: ...214 5368 522 UAE...
Страница 215: ...215 5368 522 UAE...