SD500 Spindle Servo Drive Manual
44
1: Curve 1
2: Curve2
Ones-bit: AI1
Tens-bit: AI2
Hundreds-bit: Reserved
Thousands-bit: Reserved
Table 4-26
Group F05.5x: Analog AI liner processing
Parameter code
(Address)
Designation
Content
Default
(Setting range)
Adjustable
properties
F05.50
(0x0532)
AI1 lower limit
V/F SVC FVC PMVF PMSVC PMFVC
Define the signal received at the AI1 terminal, and voltage
signals below this value are processed as the lower limit.
-100.0%
(-100.0~100.0%)
RUN
F05.51
(0x0533)
Percent of AI1 lower
limit
V/F SVC FVC PMVF PMSVC PMFVC
Set the percent of AI1 lower limit value.
-100.0%
(-100.0~100.0%)
RUN
F05.52
(0x0534)
AI1 upper limit
V/F SVC FVC PMVF PMSVC PMFVC
Define the signal received by the AI1 terminal, and voltage
signals above this value are processed as the upper limit.
100.0%
(-100.0~100.0%)
RUN
F05.53
(0x0535)
Percent of AI1 upper
limit
V/F SVC FVC PMVF PMSVC PMFVC
Set the percent of AI1 upper limit value.
100.00%
(0.00~100.00%)
RUN
F05.54
(0x0536)
AI1 filter time
V/F SVC FVC PMVF PMSVC PMFVC
Set the filter for the analog signal to eliminate interfering
signals.
0.010s
(0.000~6.000s)
RUN
F05.55
(0x0537)
AI2 lower limit
V/F SVC FVC PMVF PMSVC PMFVC
Define the signal received by the AI2 terminal, and any
voltage signal below this value is processed as the lower limit.
0.0%
(0.0~100.0%)
RUN
F05.56
(0x0538)
Percent of AI2 lower
limit
V/F SVC FVC PMVF PMSVC PMFVC
Set the percent of AI2 lower limit.
0.00%
(-100.00~100.00%)
RUN
F05.57
(0x0539)
AI2 upper limit
V/F SVC FVC PMVF PMSVC PMFVC
Define the signal received by the AI2 terminal, and voltage
signals above this value are processed as upper limit values.
100.0%
(0.0~100.0%)
RUN
F05.58
(0x053A)
Percent of AI2 upper
limit
V/F SVC FVC PMVF PMSVC PMFVC
Set the percent of AI2 upper limit.
100.00%
(-100.00~100.00%)
RUN