SD500 Spindle Servo Drive Manual
51
F06.64
(0x0640)
vX terminal valid status
source
V/F SVC FVC PMVF PMSVC PMFVC
0: Internal link with virtual vYn
1: Link with physical terminal Xn
2: Set via the function code
Ones-bit: Virtual vX1
Tens-bit: Virtual vX2
Hundreds-bit: Virtual vX3
Thousands-bit: Virtual vX4
0000
(0000~2222)
RUN
F06.65
(0x0641)
Set virtual vX terminal to
valid status via function
code
V/F SVC FVC PMVF PMSVC PMFVC
0: invalid; 1: valid
Ones-bit: VirtualvX1
Tens-bit: VirtualvX2
Hundreds-bit: Virtual vX3
Thousands-bit:
Virtual vX4
0000
(0000~1111)
RUN
F06.66
(0x0642)
Virtual vY1 output
selection
V/F SVC FVC PMVF PMSVC PMFVC
See Y terminal functions.
0
(0~31)
RUN
F06.67
(0x0643)
Virtual vY2 output
selection
V/F SVC FVC PMVF PMSVC PMFVC
See Y terminal functions.
0
(0~31)
RUN
F06.68
(0x0644)
Virtual vY3 output
selection
V/F SVC FVC PMVF PMSVC PMFVC
See Y terminal functions.
0
(0~31)
RUN
F06.69
(0x0645)
Virtual vY4 output
selection
V/F SVC FVC PMVF PMSVC PMFVC
See Y terminal functions.
0
(0~31)
RUN
F06.70
(0x0646)
vY1 output ON delay time
V/F SVC FVC PMVF PMSVC PMFVC
Set vY1 output ON delay time.
0.010s
(0.000~60.000s)
RUN
F06.71
(0x0647)
vY2 output ON delay time
V/F SVC FVC PMVF PMSVC PMFVC
Set vY2 output ON delay time.
0.010s
(0.000~60.000s)
RUN
F06.72
(0x0648)
vY3 output ON delay time
V/F SVC FVC PMVF PMSVC PMFVC
Set vY3 output ON delay time.
0.010s
(0.000~60.000s)
RUN
F06.73
(0x0649)
vY4 output ON delay time
V/F SVC FVC PMVF PMSVC PMFVC
Set vY4 output ON delay time.
0.010s
(0.000~60.000s)
RUN
F06.74
(0x064A)
vY1 output OFF delay
time
V/F SVC FVC PMVF PMSVC PMFVC
Set vY1 output OFF delay time.
0.010s
(0.000~60.000s)
RUN
F06.75
vY2 output OFF delay
V/F SVC FVC PMVF PMSVC PMFVC
0.010s
RUN