ASFIFF12 High Speed
vacon • 49
24-hour s358 (0)40 837 1150 • Email: [email protected]
721
Automatic restart: Number of tries after overvoltage trip
(2.8.5)
This parameter determines how many automatic restarts can be made during the trial
time set by parameter
after an overvoltage trip.
0
= No automatic restart after overvoltage fault trip
>0
= Number of automatic restarts after overvoltage fault trip. The fault is
reset and the drive is started automatically after the DC-link voltage
has returned to the normal level.
722
Automatic restart: Number of tries after overcurrent trip
(2.8.6)
(NOTE! IGBT temp fault also included)
This parameter determines how many automatics restarts can be made during the trial
time set by
.
0
= No automatic restart after overcurrent fault trip
>0
= Number of automatic restarts after overcurrent trip, saturation trip
and IGBT temperature faults.
723
Automatic restart: Number of tries after 4mA reference trip
(2.8.7)
This parameter determines how many automatics restarts can be made during the trial
time set by
.
0
= No automatic restart after 4mA reference fault trip
>0
= Number of automatic restarts after the analogue current signal
(4…20mA) has returned to the normal level (>4mA)
725
Automatic restart: Number of tries after external fault trip
(2.8.9)
This parameter determines how many automatics restarts can be made during the trial
time set by
.
0
= No automatic restart after External fault trip
>0
= Number of automatic restarts after External fault trip
726
Automatic restart: Number of tries after motor temperature fault trip
(2.8.8)
This parameter determines how many automatics restarts can be made during the trial
time set by
.
0
= No automatic restart after Motor temperature fault trip
>0
= Number of automatic restarts after the motor temperature has
returned to its normal level
727
Response to undervoltage fault
(2.7.5)
0
= Fault stored in fault history
1
= Fault not stored in fault history
For the undervoltage limits, see the product’s User’s Manual, Table 4-4.