ASFIFF12 High Speed
vacon • 5
24-hour s358 (0)40 837 1150 • Email: [email protected]
Jum per block X 3 :
CM A a nd CM B grounding
CMB connected to GN D
CMA connected to GN D
CMB isolated from GN D
CMA isolated from GN D
CMB and CMA
internally connected together,
isolated from GN D
= Factory default
3. CONTROL
I/O
NXOPTA1
Terminal Signal
Description
1 +10V
ref
Reference output
Voltage for potentiometer, etc.
2
AI1+
Analogue input, voltage range
0—10V DC
Voltage input frequency reference
3
AI1-
I/O Ground
Ground for reference and controls
4 AI2+
5 AI2-
Analogue input, current range
0—20mA
Current input frequency reference
6
+24V
Control voltage output
Voltage for switches, etc. max 0.1 A
7
GND
I/O ground
Ground for reference and controls
8 DIN1 Start
forward
(programmable)
Contact closed = start forward
9 DIN2 Start
reverse
(programmable)
Contact closed = start reverse
10 DIN3 External
fault
input
(programmable)
Contact open = no fault
Contact closed = fault
11 CMA
Common for DIN 1—DIN 3
Connect to GND or +24V
12
+24V
Control voltage output
Voltage for switches (see #6)
13
GND
I/O ground
Ground for reference and controls
14
DIN4
Multi-step speed select 1
DIN4
DIN5
Frequency ref.
15
DIN5
Multi-step speed select 2
Open
Closed
Open
Closed
Open
Open
Closed
Closed
Ref.U
in
Multi-step ref.1
Multi-step ref.2
Ref.I
in
16
DIN6
Fault reset
Contact open = no action
Contact closed = fault reset
17
CMB
Common for DIN4—DIN6
Connect to GND or +24V
18 AO1+
19 AO1-
Output frequency
Analogue output
Programmable
Range 0—20 mA/R
L
, max. 500
Ω
20 DO1 Digital
output
READY
Programmable
Open collector, I
≤
50mA, U
≤
48 VDC
NXOPTA2
21
RO1
22
RO1
23
RO1
Relay output 1
RUN
Programmable
24
RO2
25
RO2
26
RO2
Relay output 2
FAULT
Programmable
Table 3-1. Standard application default I/O configuration.
Note:
See jumper selections below.
More information in the product’s
User's Manual.
READY
RUN
220
VAC
mA
Reference potentiometer,
1…10 k
Ω