300
Start/Stop logic selection
(2.2.1)
0
DIN1: closed contact = start forward
DIN2:
closed
contact = start reverse
Figure 5-3. Start forward/Start reverse
c
The first selected direction has the highest priority.
d
When the DIN1 contact opens the direction of rotation starts the change.
e
If Start forward (DIN1) and Start reverse (DIN2) signals are active simultaneously
the Start forward signal (DIN1) has priority.
1
DIN1: closed contact = start
open contact = stop
DIN2: closed contact = reverse
open contact = forward
See
below.
Figure 5-4. Start, Stop, Reverse
2
DIN1: closed contact = start
open contact = stop
DIN2: closed contact = start enabled open contact = start disabled and drive stopped
if running
1
2
3
t
NX12K09
Output
frequency
Stop function
(ID506)
= coasting
FWD
REV
DIN1
DIN2
t
NX12K10
Output
frequency
Stop function
(ID506)
= coasting
FWD
REV
DIN1
DIN2