DESCRIPTION OF PARAMETERS
On the following pages you will find the parameter descriptions arranged according to the individual
ID number of the parameter. A shaded parameter ID number (e.g.
377 AI1 Signal SelectionP
)
indicates that the
TTF programming method
shall be applied to this parameter.
101
Minimum frequency
(2.1.1)
102 Maximum
frequency
(
2.1.2)
Defines the frequency limits of the frequency converter.
The maximum value for these parameters is 5200 Hz.
The software will automatically check the values of parameters ID105, ID106,
.
103
Acceleration time 1
(2.1.3)
104
Deceleration time 1
(2.1.4)
These limits correspond to the time required for the output frequency to
accelerate from the zero frequency to the set maximum frequency (P ID102).
105
Preset speed 1
(2.1.14)
106
Preset speed 2
(2.1.15)
Parameter values are automatically limited between the minimum and maximum
frequencies (P ID101, ID102).
Note the use of TTF-programming method in the Multi-purpose Control Application. See
parameters
.
Speed
Multi-step speed
sel. 1 (DIN4)
Multi-step speed
sel. 2 (DIN5)
Basic speed
0
0
ID105 1
0
ID106 0
1
Table 5-1. Preset speed
107 Current
limit
(2.1.5
)
This parameter determines the maximum motor current from the frequency converter.
The parameter value range differs from size to size.
NOTE! The Max value for this parameter might differ for FR9 and bigger and for NXLC.