52 • vacon
ASFIFF12 High Speed
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
850
Fieldbus reference minimum scaling
(2.9.1)
851
Fieldbus reference maximum scaling
(2.9.2)
Use these two parameters to scale the fieldbus reference signal.
If ID850 = ID851 then custom scaling is not used and the minimum and maximum
frequencies are used for scaling.
The scaling takes place as presented in Figure 5-6. See also chapter 6.6.
Note:
Using this custom scaling function also affects the scaling of the actual value.
852 to
859
Fieldbus data out selections 1 to 8
(2.9.3 to 2.9.10)
Using these parameters, you can monitor any monitoring or parameter value from the
fieldbus. Enter the ID number of the item you wish to monitor for the value of these
parameters. See chapter 6.6.
See monitoring signals for full detail of ID numbers
Some typical values:
1
Output frequency
15
Digital inputs 1,2,3 statuses
2
Motor speed
16
Digital inputs 4,5,6 statuses
3
Motor current
17
Digital and relay output statuses
4
Motor torque
25
Frequency reference
5
Motor power
26
Analogue output current
6 Motor
voltage
27 AI3
7
DC link voltage
28
AI4
8
Unit temperature
31
AO1 (expander board)
9
Motor temperature
32
AO2 (expander board)
13
AI1
37
Active fault 1
14 AI2
45
Motor current (drive independent)
given with one decimal point
Table 5-7.
1355 to
1369 Flux
10…150%
Motor voltage corresponding to 10%….150%c of flux as a percentage of Nominal
Flux voltage. Measured during identification.