ASFIFF12 High Speed
vacon • 31
24-hour s358 (0)40 837 1150 • Email: [email protected]
315
Output frequency limit supervision function
(2.3.101)
0
No supervision
1
Low limit supervision
2
High limit supervision
If the output frequency goes under/over the set limit (ID316) this function generates a
warning message via the digital output DO1 or via the relay output RO1
or RO2 depending on the settings of parameters
.
316
Output frequency limit supervision value
(2.3.11)
Selects the frequency value supervised by parameter ID315. See Figure 5-12
Figure 5-12. Output frequency supervision
377
AI1 signal selection
(2.2.8)
Connect the AI1 signal to the analogue input of your choice with this parameter. For
more information about the TTF programming method.
388
AI2 signal selection
(2.2.9)
Connect the AI2 signal to the analogue input of your choice with this parameter. For
more information about the TTF programming method.
f[Hz]
t
21 RO1
22 RO1
23 RO1
21 RO1
22 RO1
23 RO1
21 RO1
22 RO1
23 RO1
NX12K19
Example:
ID316
ID315 = 2