30 • vacon
ASFIFF12 High Speed
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
311
Analogue output scale 234567
(2.3.6)
Scaling factor for analogue output.
Signal
Max. value of the signal
Output frequency
Max frequency (ID102)
Freq. Reference
Max frequency (ID102)
Motor speed
Motor nom. speed
1xn
mMotor
Output current
Motor nom. current 1xI
nMotor
Motor torque
Motor nom. torque
1xT
nMotor
Motor power
Motor nom. power 1xP
nMotor
Motor voltage
100% x U
nmotor
DC-link voltage
1000 V
Table 5-4. Analogue output scaling
Figure 5-11. Analogue output scaling
312
Digital output function
(2.3.7)
313
Relay output 1 function
(2.3.83)
314
Relay output 2 function
(2.3.9)
Setting value
Signal content
0 = Not used
Out of operation
Digital output DO1 sinks the current and
programmable relay (RO1, RO2) is activated when:
1 = Ready
The frequency converter is ready to operate
2 = Run
The frequency converter operates (motor is running)
3 = Fault
A fault trip has occurred
4 = Fault inverted
A fault trip not occurred
5 = Vacon overheat warning
The heat-sink temperature e70
°
C
6 = External fault or warning
Fault or warning depending on P
7 = 4mA reference fault or warning
Fault or warning depending on P
- if analogue reference is 4—20 mA and signal is <4mA
8 = Warning
Always if a warning exists
9 = Reversed
The reverse command has been selected
10 = Preset speed 1 (Applications 2)
10 = Jogging speed (Applications 3456)
The preset speed has been selected with digital input
The jogging speed has been selected with digital
input
11 = At speed
The output frequency has reached the set reference
12 = Motor regulator activated
Overvoltage or overcurrent regulator was activated
13 = Output frequency limit supervision
The output frequency goes outside the set
supervision low limit/high limit (see parameter ID's
and
below)
14 = Control from I/O terminals (Appl. 2)
I/O control mode selected (in menu M3)
15 = Thermistor fault or warning (Appl.2)
The thermistor input of option board indicates
overtemperature. Fault or warning depending on par
16 = Fieldbus input data
Fieldbus input data (FBFixedControlWord) to DO/RO.
Table 5-5. Output signals via DO1 and output relays RO1 and RO2.
1.0
0
20 mA
4 mA
10 mA
0.5
0 mA
NX12K18
12 mA
ID310 = 1
ID311 =
200%
ID311 =
100%
ID311 =
50%
ID310 = 0
Analogue
output
current
Max. value of signal
selected by ID307