56 • vacon
ASFIFF12 High Speed
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
5.1
Keypad control parameters
Unlike the parameters listed above, these parameters are located in the
M3
menu of the control
keypad. The reference parameters do not have an ID number.
114
Stop button activated
(3.4,
3.6)
If you wish to make the Stop button a "hotspot" which always stops the drive regardless
of the selected control place, give this parameter the value
1
.
See also parameter ID125.
125 Control
Place
(3.1)
The active control place can be changed with this parameter. For more information, see
the product’s User's Manual.
Pushing the
Start button
for 3 seconds selects the control keypad as the active control
place and copies the Run status information (Run/Stop, direction and reference).
123 Keypad
Direction
(3.3)
0
Forward: The rotation of the motor is forward, when the keypad is the active
control place.
1
Reverse: The rotation of the motor is reversed, when the keypad is the active
control place.
For more information, see the product’s User's Manual.
R3.2 Keypad
Reference
(3.2)
The frequency reference can be adjusted from the keypad with this parameter.
The output frequency can be copied as the keypad reference by pushing the
Stop button
for 3 seconds when you are on any of the pages of menu
M3.
For more information, see
the product’s User's Manual.