ASFIFF12 High Speed
vacon • 51
24-hour s358 (0)40 837 1150 • Email: [email protected]
739
Number of PT100 inputs in use
(2.7.24)
If you have a PT100 input board installed in your frequency converter you can choose
here the number of PT100 inputs in use. See also the Vacon I/O boards manual.
0
= Not used
1
= PT100 input 1
2
= PT100 input 1 & 2
3
= PT100 input 1 & 2 & 3
4
= PT100 input 2 & 3
5
= PT100 input 3
Note:
If the selected value is greater than the actual number of used PT100 inputs, the
display will read 200ºC. If the input is short-circuited the displayed value is –30ºC.
740
Response to PT100 fault F56
(2.7.25)
0
= No response
1
= Warning
2
= Fault, stop mode after fault according to
3
= Fault, stop mode after fault always by coasting
741
PT100 warning limit
(2.7.26)
Set here the limit at which the PT100 warning (W56) will be activated.
742 PT100
fault
limit
(2.7.27)
Set here the limit at which the PT100 fault (F56) will be activated.