ASFIFF12 High Speed
vacon • 45
24-hour s358 (0)40 837 1150 • Email: [email protected]
f
I
Par. ID710
Par. ID712
NX12k63
Stall area
Defines how much of the nominal motor load is applied.
The value can be set to 0%…100%. See chapter 6.3.
Figure 5-19. Motor temperature calculation
709 Stall
protection
(2.7.13)
0
= No response
1
= Warning
2
= Fault, stop mode after fault according to
3
= Fault, stop mode after fault always by coasting
Setting the parameter to
0
will deactivate the protection and reset the stall time counter.
See chapter 6.4.
710
Stall current limit
(2.7.14)
The current can be set to 0.1…I
nMotor
*2. For a
stall stage to occur, the current must have
exceeded this limit. See Figure 5-20. The
software does not allow entering a greater
value than I
nMotor
*2. If parameter
Nominal current of motor
is changed, this
parameter is automatically restored to the
default value (I
L
Figure 5-20. Stall characteristics settings
105%
par. ID704
Θ
= (I/I
T
)
2
x (1-e
-t/T
)
I/I
T
NX12k82
Trip area
Motor temperature
Time
Motor temperature
Time constant T
*)
*)
Changes by motor size and
adjusted with parameter ID707
Fault/warning
Motor
current